Floor Standing Load Banks – 3-Phase

FLOOR STANDING LOAD BANKS – 3 PHASE

3-phase floor standing heat load banks provide predictable electrical and heat loads. This enables the testing of the electrical and cooling systems in a controlled environment.

The intended use of a data center may be all rack mounted, all floor standing or a mixed IT load. The data center may be a hosting or co site, where racks will be deployed at a later date after testing completes.

HeatLoad floor standing units are ideal in this type of environment.

Units can be supplied on a rental only or a fully managed service. HeatLoad will install and manage the load banks for the duration of the testing and de-install at the end of the test.

Additional or bespoke power cables can be supplied to increase the overall length. ‘Open’ power cables can be supplied to allow direct connection to site distribution or PDUs.

heaters-2803505178-1520347476844.jpg

Specifications
9KW 15KW 22KW
Input 400v 50Hz 400v 50Hz 400v
Connection (5-pin commando) 16 or 32Amp 32Amp 32Amp
Consumption 3 x 13Amp 3 x 22Amp 3 x 32Amp
Protection IPX4 IPX4 IPX4
Power Lead 5m 2.5, 5 or 10m 2.5, 5 or 10m
Heater Power (kw) 4.5/9 7.5/15 11/22
Kcal/Hour 3,870/7,740 6,450/12,900 9,460/18920
Air Volume (m3/hour) 780 990 2,200
Supply Air Thermostat Cut-Out 35°C 35°C 35°C
Dimensions (HxWxD) 54x44x34cm 53x38x48cm 67x59x52cm
Weight 11kg 16kg 24kg